1. Why Standard On-Grid Solar Cannot Run Directly With a DG Set
During a utility power outage, factories, hospitals, and commercial buildings switch over to captive Diesel Generators (DG). If a standard on-grid solar inverter synchronizes to the DG bus without active control and daytime solar exceeds building load, surplus power flows backwards into the DG alternator—triggering reverse-power relay trips or damaging the generator.
2. How a DG-PV Synchronization Controller Solves This
A dedicated DG-PV synchronization controller monitors live load via Current Transformers (CTs) on both the utility incomer and DG incomer. When the premises runs on DG power, the controller dynamically throttles the solar inverters via RS485/Modbus so that:
- Zero reverse power ever feeds back into the DG set.
- The DG set maintains its manufacturer-recommended minimum loading (typically ≥30% of rated kVA) to prevent wet-stacking and carbon buildup.
- Solar offsets the remaining daytime load cleanly, reducing diesel fuel burn during extended grid outages.
3. Zero-Export Behind-the-Meter Operation
The same CT-based export-limiting architecture enables 100% behind-the-meter self-consumption in zones where utility net-metering export is temporarily restricted.